Reusing the ANL or MRBF fuse from the lead-acid install.
Check its interrupt rating against the new bank's short-circuit current. Usually it does not meet it.
Sizing
Fit a Class-T fuse, or an equivalent with a high interrupt rating, at each pack's positive terminal. LiFePO4 can deliver short-circuit currents in the thousands of amps, which a standard MRBF or ANL fuse may not interrupt safely.
The amp rating is when the fuse opens. The interrupt rating is the largest fault current it can open safely without arcing across. On a lithium bank the second number is the one that matters, and it is the one not printed on the front.
The fuse goes at the pack's positive terminal, as close to it as practical. A fuse further down the run leaves the cable between the terminal and the fuse unprotected, and that is the cable nearest the energy.
Three 200 Ah packs behind one fuse at the bus is not a protected bank: a fault inside one pack is fed by the other two through their own cables. Each pack gets its own fuse.
The fuse protects the cable. Choose the closest rating to what the cable can carry — oversizing does not protect it and undersizing nuisance-trips. Bigger is not safer here.
The bank fuse protects the main run. Inverters, windlasses and distribution panels each need their own appropriately sized protection downstream.
Reusing the ANL or MRBF fuse from the lead-acid install.
Check its interrupt rating against the new bank's short-circuit current. Usually it does not meet it.
One fuse at the bus for a bank of parallel packs.
One fuse per pack, at the pack.
More on sizing
Take the load estimate, charging sources and cable runs to a qualified marine electrician. Our installation guide helps you ask about isolation, over-current protection, ventilation and compliance before work begins.