Using the fridge's rated current for 24 hours a day.
Apply its duty cycle. Most marine fridges run between 35% and 55% depending on climate and insulation.
Sizing
Multiply each load's current in amps by the hours it genuinely runs in a day, then add them up. A 5 A fridge cycling at 45% duty is 5 × 10.8 = 54 Ah, not 5 × 24.
Fridge, freezer, cabin and nav lights, instruments and chartplotter, VHF and AIS on standby, fans, water and shower pumps, and device charging. The standby loads are small individually and are the ones most often left out.
If the label gives watts, divide by the system voltage — use 12.8 V for a 12 V lithium bank and 25.6 V for a 24 V one, since that is the nominal voltage LiFePO4 actually sits at. A 60 W fridge on a 12 V bank is about 4.7 A.
Anything thermostatic runs at a duty cycle. A fridge at 45% duty over a full day is 10.8 hours of compressor time. Estimating 24 hours will roughly double your bank and your budget.
Amps × hours for each load gives amp-hours. Add them. This total is your daily draw, and every other number in the system derives from it.
An inverter for a kettle at 85 A for 18 minutes is about 25 Ah, and a watermaker at 25 A for 90 minutes is about 38 Ah. Keep these as a separate line so you can size for the days you use them and the days you do not.
The same appliance draws half the current at twice the voltage. If you have listed everything at 12 V and are sizing a 24 V bank, scale the amp figures by 0.5 before totalling.
Using the fridge's rated current for 24 hours a day.
Apply its duty cycle. Most marine fridges run between 35% and 55% depending on climate and insulation.
Mixing watts and amps in the same total.
Convert everything to amps at the system's nominal voltage first.
More on sizing
Take the load estimate, charging sources and cable runs to a qualified marine electrician. Our installation guide helps you ask about isolation, over-current protection, ventilation and compliance before work begins.